The OTIS GOEC escalator control system monitors a range of safety devices, electrical signals and mechanical operating conditions. When an abnormal condition is detected, the system may stop the escalator and display a fault message through the Service Tool or Operation / Control Panel.
Understanding these fault indications helps maintenance personnel narrow down the source of a problem and identify the appropriate inspection points.
This guide organizes the 13 fault categories covered in the supplied technical material, including the original display codes, possible causes and corresponding troubleshooting methods.
Important: The codes and procedures below follow the supplied reference document. Actual equipment configurations may vary. Inspection, reset and component replacement must be performed by qualified escalator technicians in accordance with the applicable service documentation.
1. Missing Step Detection
Fault codes
|
Detection location |
Service Tool display |
Operation / Control Panel |
| Upper landing | 0100 MSD IEU B25 | OTIS B25 |
| Lower landing | 0101 MSD IEL B26 | OTIS B26 |
Possible causes
This fault may occur when a step has been removed during maintenance and not reinstalled. An incorrectly adjusted sensor may also trigger the missing-step detection device.
The reference document specifies a distance of approximately 4 mm between the sensor surface and the step-wheel bearing.
When the safety device detects a missing step, the ECB board receives the signal and stops the escalator.
Troubleshooting
Check that all steps have been correctly installed.
Inspect and adjust the sensor position according to the equipment specification.
After correcting the underlying problem, follow the approved procedure to reset the ECB board.
2. Landing Plate Detection
Fault codes
|
Detection location |
Service Tool display |
Operation / Control Panel |
| Upper landing plate | 0102 FPC UAC S5 | OTIS S05 |
| Lower landing plate | 0103 FPC MAC S6 | OTIS S06 |
Possible cause
When a landing plate is lifted, the detection rod resets and activates the associated safety switch. The ECB board then receives the signal and stops the escalator.
Troubleshooting
Inspect the clearance between the landing-plate switch and the landing plate. Adjust the distance in accordance with the equipment requirements and verify the switch operation.
3. RSFF Board and Wiring Fault Monitoring
Fault indication
Service Tool: 0104 FfCode xxxx
Operation / Control Panel: OTIS xxxx
The actual xxxx value depends on the detected fault.
Possible causes
The supplied material identifies two main possibilities:
A fault in the safety-circuit wiring.
An incorrect RSFF address setting.
Troubleshooting
Step 1: Check ECB software settings.
Connect the service tool, enter the Adjust interface and select 1-3-4 to access the I/O settings page. Check that the relevant addresses have been entered correctly.
Step 2: Read the RSFF fault code.
In the Adjust interface, select 1-1-3 and record the displayed RSFF xxxx value.
According to the reference material, the first two digits represent the upper-landing FCODE, while the last two represent the lower-landing FCODE.
For example, RSFF 0415 indicates upper-landing FCODE 04 and lower-landing FCODE 15.
Step 3: Check the fault-state indicators.
Select 1-1-2 in the Adjust interface. Use the down-arrow key to reach pages five and six, where the indicators fu1–fu4 and fl1–fl4 are displayed.
fu refers to the upper landing.
fl refers to the lower landing.
Uppercase letters represent binary 1; lowercase letters represent binary 0.
For example, fu1, FU2, FU3, fu4 represents the binary pattern 0110, corresponding to FCODE 06. The same pattern for the fl indicators represents lower-landing FCODE 06.
If the wiring and settings have been checked but the fault remains, the reference material recommends replacing the RSFF board.
4. Brake Lining Wear Detection
Fault codes
|
Condition |
Service Tool display |
Operation / Control Panel |
| Brake lining 1 wear | 0105 BLWDweraS32 | OTIS S32 |
| Brake lining 2 wear | 0110 BLWDweraS31 | OTIS S31 |
Possible cause
When the brake lining wear detection device identifies wear, it sends a corresponding signal. The reference states that when the escalator reaches 999 starts under this condition, the ECB board prevents power from being supplied to the main motor through the main contactor.
Troubleshooting
Inspect the brake linings and replace worn linings as required. Confirm that the braking system is in proper working condition before returning the escalator to service.
5. Main Motor Overtemperature
Fault indication
Service Tool: 0106 Motortem.B2
Operation / Control Panel: OTIS GR6 on the six-group display, or OTIS B2 on the 30-fault display.
Possible cause
The reference material states that when the main motor winding temperature exceeds 155°C, the thermal switch changes state and sends a signal to the ECB board, causing the escalator to stop.
Troubleshooting
After the motor has cooled, qualified technicians should:
Check whether excessive brake tightness is causing heat buildup during operation.
Inspect internal motor wiring for short circuits.
Check whether connector P6 on the ECB board is loose.
Inspect the motor windings for damage or burnout.
Do not restart the escalator until the cause of overheating has been identified and addressed.
6. Brake Lifting Mechanism Monitoring
Fault codes
|
Condition |
Service Tool display |
Operation / Control Panel |
| Left brake lifting mechanism | 0108 No lift S33 or 0109 No fall S33 | OTIS S33 or OTIS S34 |
| Right brake lifting mechanism | 0108 No lift S34 or 0109 No fall S34 | OTIS S33 or OTIS S34 |
Possible cause
The monitoring device detects that the brake arm has not moved as expected. This may mean that the brake fails to release when the motor starts or fails to engage when the motor stops.
The ECB board then prevents the main motor from receiving power through the main contactor.
Troubleshooting
Inspect the brake electromagnet and replace it if defective.
Check and adjust the clearance between the safety switch and the actuating rod.
Verify that the relevant ECB parameter settings are correct.
7. Power Supply Monitoring
Fault codes
|
Condition |
Service Tool display |
Operation / Control Panel |
| Line voltage monitoring | 0111 Voltage ASN | OTIS ASN on the 30-fault display; OTIS GR6 on the six-group display |
| Reversed phase sequence | 0112 Phase rev J | OTIS J on the 30-fault display; OTIS GR6 on the six-group display |
Possible causes
The reference material identifies phase loss, incorrect phase sequence and undervoltage as conditions that can cause the escalator to stop.
Troubleshooting
Verify that the incoming power supply is normal.
Check the connections of the main supply conductors L1, L2, L3 and N.
Confirm the phase sequence and correct any wiring issue according to the approved electrical procedure.
Electrical measurements and wiring work must be performed by qualified personnel.
8. Reverse-Direction Protection
Fault indication
Service Tool: 0113 MotorB1 NRD
Operation / Control Panel: OTIS NRD
Possible cause
The protection device detects insufficient speed during upward operation or a tendency for the escalator to move in the opposite direction. The ECB board receives the signal and stops the escalator.
Troubleshooting
Check the main motor power wiring and resolve any wiring faults.
Inspect the motor speed sensor and replace it if defective.
Check the sensor installation gap. The sensor must not be positioned too close to or too far from the motor brake disc.
After correcting the fault, follow the approved ECB reset procedure.
9. Simultaneous UP and DOWN Logic Error
Fault indication
Service Tool: 0114 up&dwn E12
Operation / Control Panel: OTIS E12
Possible causes
The UP and DOWN relays are energized simultaneously. Incorrect operation, such as pressing the UP and DOWN buttons at the same time, may also produce this condition.
Troubleshooting
Inspect ECB board diodes D1 and D2 for damage or breakdown.
Check the key-switch signal wiring for short circuits.
Replace defective components only after confirming the fault.
10. Missing UP or DOWN Logic Signal During Operation
Fault indication
Service Tool: 0115 up&dwn E11
Operation / Control Panel: OTIS E11
Possible causes
The supplied material identifies the following possibilities:
The key switch was operated too quickly, preventing the UP or DOWN relay from energizing.
A fault exists in the key-switch wiring.
The UP or DOWN relay is not operating correctly.
Troubleshooting
Operate the key switch for approximately 1–2 seconds, as specified in the reference material.
Inspect the key-switch wiring and correct any faults.
Check the UP and DOWN relays and replace defective relays or the ECB board when the diagnosis confirms the need.
11. Inspection-Mode Logic Error: KSU or KSD
Fault indication
Service Tool: 0116 KS_INS E14
Operation / Control Panel: OTIS E14
Possible cause
The supplied material associates this fault with an improperly inserted dummy plug or an inspection socket that remains connected to the inspection box while the key switch is operated.
Troubleshooting
Check that the dummy plug is correctly inserted into the inspection socket before proceeding, following the applicable service instructions.
12. Emergency Brake Not Lifted
Fault indication
Service Tool: 0117 Emer.Br.S53
Operation / Control Panel: OTIS S53
Possible causes
The reference material lists three possible situations:
The escalator is operated downward on its first run after a power interruption when equipped with an auxiliary brake.
The auxiliary brake fails to reset within five seconds during upward operation.
The auxiliary brake activates unexpectedly while the escalator is running.
Troubleshooting
Follow the prescribed upward-operation reset procedure where applicable.
Check and adjust the position of the auxiliary-brake reset blade.
Inspect relays K02 and K02.1 and the electromagnet; replace defective components as required.
13. Emergency Brake Relay Monitoring
Fault indication
Service Tool: 0118 Emer.Re.K02
Operation / Control Panel: OTIS K02
Possible causes
The reference material identifies auxiliary-brake relay self-latching as a possible cause.
Troubleshooting
Inspect relays K02 and K02.1 and replace them if defective.
Check the auxiliary-brake wiring and correct any faults.
Check timer relay K067. The supplied reference specifies a 2-second setting.
Once the underlying fault has been corrected, follow the approved procedure to reset the ECB board.
Maintenance Recommendations
When diagnosing an OTIS GOEC escalator fault, maintenance personnel should begin with the exact fault indication and the operating condition in which it occurred. A single display code may point to a monitoring circuit, sensor, wiring issue or mechanical condition, so the displayed code should guide inspection rather than replace it.
A practical diagnostic sequence is:
Record the complete Service Tool and control-panel fault indications.
Identify the affected safety device or monitored function.
Inspect the relevant mechanical components, sensors, wiring and control-board settings.
Correct the confirmed cause before resetting the system.
Verify the relevant safety functions and operation in accordance with the manufacturer’s procedures.
Safety note: Never bypass safety devices or repeatedly reset a fault without identifying its cause. Brake, motor, power-supply and safety-circuit inspections must be carried out by qualified escalator personnel.
Conclusion
The 13 fault categories covered in this guide illustrate how the OTIS GOEC control system monitors step installation, landing plates, brake condition, motor temperature, power supply, direction of travel and emergency braking.
Accurate fault-code interpretation, systematic inspection and correct corrective action help maintenance teams identify problems more efficiently while maintaining escalator safety.